Type MC

Metal-Clad Cable | 600V | 90°C Insulation | Copper Conductor

Specifications

Size

No. of Strands

Ground Wire Size

Outside Diameter

Allowable Amperage at 60°C*

Insulation Thickness

Approx. Weight

PVC

Nylon

(AWG or kcMil)

(AWG)

(in)

(lb/1000 ft)

75°C

Size

90°C

14/2-G

1 (Solid)

1 (Solid)

14

0.015

0.004

0.495

112

20

14

12/2-G

0.015

0.004

0.430

83

20

25

14/3-G

1 (Solid)

14

0.015

0.004

0.465

103

20

25

14/4-G

25

1 (Solid)

12

0.015

0.004

0.475

103

25

30

12/3-G

1 (Solid)

12

0.015

0.004

0.505

136

25

12/4-G

30

1 (Solid)

12

0.015

0.004

0.540

165

10/2-G

25

30

1 (Solid)

10

0.020

0.004

0.535

157

10/3-G

10/4-G

35

40

1 (Solid)

10

0.020

0.004

0.580

197

35

40

7

10

0.020

0.004

0.625

240

8/2-G

35

40

7

10

0.030

0.005

0.645

232

8/3-G

50

55

7

10

0.030

0.005

0.680

300

50

55

6/2-G

7

8

0.030

0.005

0.715

315

65

75

6/3-G

7

8

0.030

0.005

0.820

443

65

75

*
Ampacity of conductors are based on NFPA 70 (NEC) Table 310.16. See 110.14(C), 240.4(D) and 310.15(B) and (C) for other limitations where applicable. Note: Additional ampacity limitations, adjustments or corrections may apply per 310.15 and 240.4 of the NEC.

Standards

  • UL-83, UL-1569, UL-1581, UL-2556; NFPA 70 (NEC®) Article 334; ASTM-B-566; NEMA RV 2-2011

Listings

  • UL: E515494, E516194

Construction

  • Conductors – Sizes 14-10 AWG: solid, annealed THHN copper with solid copper ground; sizes 8 AWG and larger: stranded, annealed copper with solid copper ground
  • Conductor Insulation – Color-coded Polyvinyl Chloride (PVC) compound meeting the required thickness of Type THHN/THWN with a heat-stabilized nylon jacket rated for 90°C in dry locations
  • Metal-Clad Armor – Lightweight aluminum interlocking armor

Applications

  • Commercial buildings in raceways, walls with metal studs and cable trays
  • Suitable for large places of public assembly, industrial manufacturing facilities and processing plants
  • Theaters (Article 520), motion picture/TV studios (Article 530), and assembly spaces with over 100 people (Article 518)
  • Secondary feeders in industrial and commercial distribution systems; supplying electricity to station auxiliaries in power stations; in approved raceways or as open run; cable trays; exposed or concealed
  • Handles branch, feeder and service circuits (Articles 230-243)
  • Class I, Div. 2, Class II, Div. 2 and Class III, Div. 1 hazardous locations

Ordering Info

Size


Conductor Color Sequence*

Standard Packaging
**

(AWG or kcMil)

Part Number
***

BK, WT, RD, BL, GR (G)

500’, 1000’, 2500’

BK, WT, GR (G)

500’, 1000’, 2500’

14/2MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, RD, GR (G)

14/4-G

500’, 1000’, 2500’

14/3MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

14/2-G

14/4MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, GR (G)

500’, 1000’, 2500’

12/2MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, RD, GR (G)

14/3-G

500’, 1000’, 2500’

12/3MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, RD, BL, GR (G)

500’, 1000’, 2500’

12/4MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

12/2-G

BK, WT, GR (G)

500’, 1000’, 2500’

10/2MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, RD, GR (G)

500’, 1000’, 2500’

12/3-G

10/3MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, RD, BL, GR (G)

500’, 1000’, 2500’

10/4MCA-1/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, GR (G)

1000’, 2500’

8/2MCA-7/0-AL-NG-CU-[Ft]-[Pkg]

8/3-G

BK, WT, RD, GR (G)

1000’, 2500’

8/3MCA-7/0-AL-NG-CU-[Ft]-[Pkg]

6/2-G

6/3-G

BK, WT, GR (G)

1000’, 2500’

6/2MCA-7/0-AL-NG-CU-[Ft]-[Pkg]

BK, WT, RD, GR (G)

1000’, 2500’

6/3MCA-7/0-AL-NG-CU-[Ft]-[Pkg]

12/4-G

10/2-G

10/3-G

10/4-G

8/2-G

*
Insulation colors: Black (BK), White (WT), Red (RD), Blue (BL), Green (GR).
**
Other packaging options and denominations available on request. 500’ is on plastic spools [SP]; 1000’ and 2500’ are on wooden reels [WR].
***
Part Number Legend: [Size][Type]-[Strands]-[Color]-NG-[Length in Feet]-[Packaging]
Standard Packaging [Pkg]: Hand Coils [COIL], Plastic Spools [SP], Wooden Reels [WR]
UL MARKER ID TAPE LEGEND: RIVAL TYPE MC (AWG) THHN 600V (UL) E523379
ETL MARKER ID TAPE LEGEND: RIVAL TYPE MC (AWG) THHN 600V ETL 5021266 CONFORMS TO UL STANDARD 1569